Repositioning the junction box to the left or right side

Vitocal 100-WA

What is going on

The junction box is factory-mounted at the front and can be moved to the left or right side to suit the installation. Work is done inside the unit housing.

Check in this order

  1. Remove the display panel and the access panels for the side you are working on.
  2. Disconnect the display cable from the upper front access panel, since that panel moves with the junction box.
  3. Remove the four junction box retaining screws and set them aside.
  4. Turn the junction box to the desired orientation (left or right) inside the housing.
  5. Secure the junction box with the four retaining screws.
  6. Route the display cable to the display mounting location and reconnect it.
  7. Reinstall the access panels.

Applies to: Vitocal 100-WA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: vitocal_100-wa_ap1t_ios.pdf, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.