Viessmann · Heat pump troubleshooting
Replace electronic control board, PCB 6K-12K (208/230V)
What is going on
Access and removal of the control board on the 6K to 12K models with 208/230V supply.
Check in this order
- Disconnect the compressor connector and release the ground wire (1 screw).
- Pull the wires out of the electrical supporting plate and turn the electronic control assembly over.
- Remove the electronic installing box subassembly (4 hooks).
- Remove the board (2 hooks).
- Disconnect the connectors from the electronic control board.
- Remove the electronic control board (4 hooks).
Applies to: DLCSRB 6K to 12K models, 208/230V
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCSRB Service Manual, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.