Replace electronic control board, PCB 18K (208/230V)
What is going on
Access and removal of the control board on the 18K model with 208/230V supply. Several sensor and valve connectors must be disconnected.
Check in this order
- Remove the screws and loosen the hooks, then open the electronic control box cover (5 screws and 2 hooks).
- Disconnect the fan motor connector from the electronic control board.
- Remove the compressor connector.
- Pull out the two blue wires connected to the four-way valve.
- Pull out the connectors of the condenser coil temperature sensor (T3), outdoor ambient temperature sensor (T4) and discharge temperature sensor (TP).
- Disconnect the electronic expansion valve wire.
- Remove the connector for the DR and reactor.
- Remove the electronic control board.
Applies to: DLCSRB 18K model, 208/230V
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCSRB Service Manual, p. 71. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.