Remove the four-way valve (heat pump models)

Vitocal 100-SDLCURA

What is going on

Remove the panel plate and disconnect the four-way valve from the PCB before removing the sound blanket. WARNING: Evacuate the system and confirm there is no refrigerant left before removing the valve or compressor. For R32 and R290, recover refrigerant, flush with nitrogen, then repeat both steps before heating brazed parts. Only professionals should do this work.

Check in this order

  1. Heat the brazed joints and detach the four-way valve and its pipe.
  2. Remove the four-way valve assembly with pliers.

Applies to: DLCURA heat pump models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA Service Manual, p. 76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.