Viessmann · Heat pump troubleshooting
Remove the fan motor and fan
What is going on
Remove the chassis assembly first to reach the fan motor board and fan.
Check in this order
- Open the two stop blocks of the chassis assembly.
- Remove the chassis assembly along the direction shown.
- Remove the two screws and take off the fan motor board.
- Remove the bearing sleeve.
- Remove the screw.
- Pull the fan motor and fan assembly out from the side.
Applies to: DLFSHC indoor units, sizes 06 to 36
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann DLFSHC service manual, pp. 45-46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.