Viessmann · Heat pump troubleshooting

Remove the evaporator

DLFSHCH

What is going on

Remove the front panel, electrical parts and the fan before starting this procedure.

Check in this order

  1. Remove the 2 screws and then remove the panel frame assembly.
  2. Disassemble the pipe clamp board.
  3. Remove the screw on the evaporator at the left fixed plate.
  4. Remove the screw on the evaporator at the right side.
  5. Bend the piping carefully to separate the chassis assembly from the evaporator, then remove the evaporator.

Applies to: DLFSHC indoor units, sizes 06 to 36

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann DLFSHC service manual, pp. 43-44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.