Viessmann · Heat pump troubleshooting
Remove the compressor
What is going on
WARNING: Evacuate the system and confirm there is no refrigerant left before removing the four-way valve or compressor. For R32 and R290, recover refrigerant, flush with nitrogen, then repeat both steps before heating brazed parts. Only professionals should do this work.
Check in this order
- Remove the flange nut and the terminal cover.
- Disconnect the compressor connectors.
- Remove the hex nuts and washers that secure the compressor to the bottom plate.
- Heat the brazed joints and remove the discharge pipe and suction pipe.
- Lift the compressor off the base pan with pliers.
Applies to: DLCURA 18 to 60 outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA Service Manual, p. 77-78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.