Viessmann · Heat pump troubleshooting

Remove outdoor unit panels, 18K standard heat

Vitocal 100-S

What is going on

Panel removal order for the outdoor unit, 18K standard heat model.

Check in this order

  1. Turn off the air conditioner and the power breaker.
  2. Remove the handle screw (1) and then remove the handle.
  3. Remove the top cover screws (4) and then remove the top cover. One of the screws is under the handle.
  4. Remove the water collecting cover screws (2) and then remove the water collecting cover.
  5. Remove the front panel screws (7 on on/off models, or 9 on inverter models) and then remove the front panel.
  6. Remove the right panel screws (5) and then remove the right panel.

Applies to: Outdoor unit size 18K standard heat

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann DLCURA service manual, p. 53-55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.