Viessmann · Heat pump troubleshooting

Remove four-way valve (heat pump models)

Vitocal 100-SDLCSRB

What is going on

Only on heat pump models. The refrigerant must be fully removed first. For R32 and R290, evacuate with a vacuum pump, flush with nitrogen, and repeat before any brazing. Work should be done by an authorized technician.

Check in this order

  1. Evacuate the system and confirm no refrigerant is left.
  2. For R32 and R290, evacuate, flush with nitrogen, then evacuate again before heating brazed parts.
  3. Heat the brazed joints and detach the 4-way valve and its pipe.
  4. Remove the 4-way valve assembly with pliers.

Applies to: DLCSRB heat pump models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCSRB service manual, p. 76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.