Viessmann · Heat pump troubleshooting

Remove electronic control board (PCB 24K-36K, 208/230V)

Vitocal 100-SDLCSRB

What is going on

Removal of the outdoor electronic control board on the 24K to 36K sizes with 208/230V supply. Discharge the capacitors and use anti-static protection first (see the capacitor tip in this set).

Check in this order

  1. Turn off power and lock out the disconnect.
  2. Loosen the 4 hooks and open the electronic control box cover.
  3. Remove the 6 screws on the control board and turn the board over.
  4. Pull out the connectors.
  5. Remove the 4 screws and take the control board out.

Applies to: DLCSRB outdoor units, 24K-36K sizes, 208/230V

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCSRB service manual, p. 72-73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.