Remove compressor
What is going on
Remove the panel plate and the PCB compressor connection before disassembling the sound blanket. Refrigerant recovery and the R32/R290 evacuation and nitrogen flush must be done first, as in the four-way valve procedure. Work should be done by an authorized technician.
Check in this order
- Remove the terminal cover flange nut and take off the terminal cover.
- Disconnect the compressor connectors.
- Remove the hex nuts and washers that hold the compressor to the bottom plate.
- Heat the brazed joints and remove the discharge pipe and the suction pipe.
- Lift the compressor off the base pan with pliers.
Applies to: DLCSRB outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-S DLCSRB service manual, p. 77-78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.