Refrigerant removal, evacuation and purging for flammable refrigerants
What is going on
Use this sequence before opening the refrigerant circuit for repair or any other purpose.
Check in this order
- Remove the refrigerant safely following local and national rules.
- Evacuate the circuit.
- Purge with inert gas (optional for A2L).
- Evacuate again (optional for A2L).
- If flame is used to open the circuit, keep purging with inert gas throughout.
- Open the circuit.
- Purge with oxygen-free nitrogen, never compressed air or oxygen, and repeat as needed.
- Break the vacuum with nitrogen, fill to working pressure, vent to atmosphere, then pull vacuum again. Repeat until no refrigerant remains.
- Vent the system to atmospheric pressure before work starts.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
Applies to: Vitocal 100-AW AM2V refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.