Refrigerant recovery for service or decommissioning

Vitocal 100-WA

What is going on

Recover flammable refrigerant safely into the correct equipment.

Check in this order

  1. Take an oil and refrigerant sample before the task in case analysis is needed before reuse.
  2. Make sure electrical power is available before starting.
  3. Use only recovery cylinders designated and labelled for the recovered refrigerant, with a pressure-relief valve and shut-off valves in good order.
  4. Have enough cylinders for the total system charge.
  5. Evacuate and, if possible, cool empty recovery cylinders before recovery.
  6. Use recovery equipment in good working order, suitable for flammable refrigerant, with its instructions at hand.
  7. Have calibrated weighing scales available and in good working order.
  8. Use hoses with leak-free disconnect couplings in good condition.
  9. Process recovered refrigerant per local law and arrange the waste transfer note. Do not mix refrigerants.
  10. If compressors or oils are removed, evacuate them to an acceptable level first. Do not heat the compressor body with an open flame to speed this up.
  11. Drain oil safely.

Applies to: Vitocal 100-WA R-454B refrigerant circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 57. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.