Refrigerant recovery for service or decommissioning
What is going on
Recover flammable refrigerant safely into the correct equipment.
Check in this order
- Take an oil and refrigerant sample before the task in case analysis is needed before reuse.
- Make sure electrical power is available before starting.
- Use only recovery cylinders designated and labelled for the recovered refrigerant, with a pressure-relief valve and shut-off valves in good order.
- Have enough cylinders for the total system charge.
- Evacuate and, if possible, cool empty recovery cylinders before recovery.
- Use recovery equipment in good working order, suitable for flammable refrigerant, with its instructions at hand.
- Have calibrated weighing scales available and in good working order.
- Use hoses with leak-free disconnect couplings in good condition.
- Process recovered refrigerant per local law and arrange the waste transfer note. Do not mix refrigerants.
- If compressors or oils are removed, evacuate them to an acceptable level first. Do not heat the compressor body with an open flame to speed this up.
- Drain oil safely.
Applies to: Vitocal 100-WA R-454B refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.