Viessmann · Heat pump troubleshooting

Refrigerant line installation rules

Vitocal 100-S

What is going on

Limits for the interconnecting refrigerant lines between indoor and outdoor units. Standard charge covers 25 ft of line. Lines must be insulated and not buried deeper than allowed.

Check in this order

  1. Keep each run at least 10 ft (3 m) between indoor and outdoor units.
  2. Charge is factory-set for runs up to 25 ft (7.6 m). Longer runs need extra refrigerant per the piping table.
  3. Do not bury lines. If a section must be buried, bury no more than 36 in (914 mm) and provide at least a 6 in (152 mm) vertical rise to the service valves.
  4. Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Use closed-cell insulation for long-line runs.
  5. Insulate both refrigerant lines separately.
  6. Isolate the tubing from the building structure so vibration and noise are not transmitted.

Applies to: DLCURA outdoor units 18K to 60K

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA Service Manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.