Refrigerant leak checks on flammable refrigerant systems
What is going on
Do not use any open flame to look for leaks. Use detectors that suit the refrigerant and are not ignition sources.
Check in this order
- Do not use a halide torch or any naked-flame detector.
- Use an electronic leak detector rated for the refrigerant and calibrated in a refrigerant-free area. Note that its sensitivity may be lower for flammable refrigerants.
- Set leak detection to 25% of the lower flammable limit at most.
- Use leak detection fluid only if it contains no chlorine.
- Remove or put out all open flames if a leak is suspected.
- If the leak needs brazing, recover all refrigerant or isolate the leaking section with shut-off valves first.
Applies to: Vitocal 100-AW AM2V outdoor unit refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.