Weil-McLain · Heat pump troubleshooting

Pump making noise (cavitation)

ECO HP

What is going on

The pump is cavitating, usually from air or low inlet pressure.

Likely causes

  • Air in the system
  • Water pressure at pump inlet too low
  • Pressure and temperature gauge broken
  • Expansion vessel broken or pre-pressure set incorrectly

Check in this order

  1. Purge air from the system.
  2. Check the gauge for sufficient water pressure; must be above 14.5 psi with cold water.
  3. Check that the pressure and temperature gauge is not broken.
  4. Check that the expansion vessel is not broken.
  5. Check that the expansion vessel pre-pressure setting is correct.

Applies to: ECO HP heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.