Pressure relief valve installation and discharge piping

Vitocal 100-AW

What is going on

The factory-supplied pressure relief valve must be used. No isolation valve may be placed between the heat pump and the relief valve. Air is removed through air vents on the system supply. Operating range is 8 psig (0.5 bar) minimum to 30 psig (2 bar) maximum.

Check in this order

  1. Install the supplied fittings and the 30 PSI relief valve on the supply-from-outdoor-unit connection of the indoor unit.
  2. Run the discharge pipe from the relief valve to a floor drain and end it about 6 in. (150 mm) above the drain.
  3. Keep the discharge end unthreaded and do not reduce the pipe diameter.
  4. Do not install a shutoff valve in the discharge pipe.
  5. Do not pipe the discharge to the outdoors.
  6. Orient the discharge pipe so it cannot scald people.
  7. Make sure supply and return lines have no restrictive piping that could trap air.

Applies to: Indoor unit safety relief valve

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.