Pressure relief valve and discharge piping (indoor unit)

Vitocal 100-AW AM2V

What is going on

Install the factory-supplied approved 30 PSI relief valve on the supply-from-outdoor-unit connection, then pipe the discharge to a floor drain. Keep the discharge clear of anyone standing nearby.

Check in this order

  1. Use the supplied fittings to fit the 30 PSI relief valve on the supply-from-outdoor-unit connection (see piping connections on p. 22).
  2. Use only the approved factory-supplied relief valve.
  3. Do not fit any isolation valve between the heat pump and the relief valve.
  4. Thread-free end on the discharge pipe; do not reduce the discharge pipe diameter.
  5. Run the discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
  6. Orient the discharge so it cannot scald people.
  7. Do not put a shutoff valve in the discharge pipe.
  8. Never pipe the discharge to the outdoors.
  9. Make sure supply and return lines have no restrictive piping where air can get trapped; purge air through the air vents in the supply.

Applies to: Vitocal 100-AW AM2V indoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.