Viessmann · Heat pump troubleshooting
Pressure relief valve and discharge piping (indoor unit)
What is going on
Install the factory-supplied approved 30 PSI relief valve on the supply-from-outdoor-unit connection, then pipe the discharge to a floor drain. Keep the discharge clear of anyone standing nearby.
Check in this order
- Use the supplied fittings to fit the 30 PSI relief valve on the supply-from-outdoor-unit connection (see piping connections on p. 22).
- Use only the approved factory-supplied relief valve.
- Do not fit any isolation valve between the heat pump and the relief valve.
- Thread-free end on the discharge pipe; do not reduce the discharge pipe diameter.
- Run the discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Orient the discharge so it cannot scald people.
- Do not put a shutoff valve in the discharge pipe.
- Never pipe the discharge to the outdoors.
- Make sure supply and return lines have no restrictive piping where air can get trapped; purge air through the air vents in the supply.
Applies to: Vitocal 100-AW AM2V indoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.