Preparing to work on outdoor board: discharge capacitors

Vitocal IND-O

What is going on

Electrolytic capacitors keep a charge after power is off. Discharge them before touching the boards.

Check in this order

  1. Disconnect the main power and lock out the switch.
  2. Discharge the electrolytic capacitor with a discharge resistor (about 100 ohm, 40 W) or a soldering iron (plug) between the + and - terminals on the back side of the outdoor PCB.
  3. Confirm the capacitor is discharged before touching the board.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH service manual, PDF p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.