Preparing the refrigerant circuit for service
What is going on
Steps to complete before opening or working on the refrigerant circuit. The unit uses R-454B, which is heavier than air and forms explosive mixtures.
Check in this order
- Check the refrigerant circuit for leaks.
- Make sure the room is very well ventilated, especially at floor level, and keep it that way for the whole job.
- Secure the work area and warn maintenance staff and people nearby about the work.
- Remove all flammable and movable materials and ignition sources from the area around the heat pump.
- Check the surrounding air for escaping refrigerant before, during and after the work, using an explosion-proof detector rated for R-454B that cannot create sparks.
- Keep a CO2 or dry powder extinguisher at hand when draining refrigerant, topping up refrigerant, or brazing or welding.
- Post no-smoking signs.
Applies to: Vitocal 100-WA
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: vitocal_100-wa_ap1t_ios.pdf, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.