Viessmann · Heat pump troubleshooting
Outdoor unit panel removal, sizes 24K to 36K (208/230V)
What is going on
Order of panel removal for the 24K to 36K outdoor units. Photos are for reference and may differ from the actual unit.
Check in this order
- Turn off the air conditioner and the power breaker.
- Remove the handle screws (2) and take off the handle.
- Remove the top cover screws (4); two are under the handle. Lift off the top cover.
- Remove the front right panel screws (2) and take off the front right panel.
- Remove the front panel screws (9) and take off the front panel.
Applies to: DLCSRB sizes 24K, 30K and 36K (208/230V)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann DLCSRB service manual, p. 62-63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.