Viessmann · Heat pump troubleshooting

Outdoor unit panel removal, sizes 12 (115V) and 6-12K (208/230V)

Vitocal 100-SDLCSRB

What is going on

Order of panel removal for the outdoor unit. Photos in the manual are for reference and may differ from the actual unit.

Check in this order

  1. Turn off the air conditioner and the power breaker.
  2. Remove the handle screw (1) and take off the handle.
  3. Remove the top cover screws (4); one is under the big handle. Lift off the top cover.
  4. Remove the water collecting cover screws (2) and take off the water collecting cover.
  5. Remove the front panel screws 7 screws on on/off models, 9 screws on inverter models. Take off the front panel.
  6. Remove the right panel screws (5) and take off the right panel.

Applies to: DLCSRB sizes 06 to 12 (12 at 115V; 6-12K at 208/230V)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann DLCSRB service manual, p. 56-58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.