Viessmann · Heat pump troubleshooting
Outdoor unit 36K high heat, 48K standard and high heat, 60K standard and high heat - initial disassembly
What is going on
First steps for the larger outdoor units. The sequence continues beyond the extracted pages, so later steps are not available here.
Check in this order
- Turn off the air conditioner and the power breaker.
- Remove the handle screws (2), then remove the handle.
- Remove the top cover screws (4), then remove the top covers. Two of the screws are located under the handle.
- Remove the water collecting cover screws (2), then remove the water collecting cover.
Applies to: Outdoor unit sizes 36K high heat, 48K standard and high heat, 60K standard and high heat
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA Service Manual, p. 64 of 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.