Outdoor unit 24K high heat, 30K standard and high heat, 36K standard heat - panel and net disassembly

Vitocal 100-S DLCURA

What is going on

Disassembly of the handle, top cover, front panels, water collecting cover, rear net and right panel.

Check in this order

  1. Turn off the air conditioner and the power breaker.
  2. Remove the handle screws (2), then remove the handle. Two of the screws are located under the handle.
  3. Remove the top cover screws (4), then remove the top cover.
  4. Remove the front panel screws (2) and then remove the front right panel.
  5. Remove the front panel screws (9), then remove the front panel.
  6. Remove the water collecting cover screws (2), then remove the water collecting cover.
  7. Remove the rear net screws (2), then remove the rear net.
  8. Remove the right panel screws (8), then remove the right panel.

Applies to: Outdoor unit sizes 24K high heat, 30K standard and high heat, 36K standard heat

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA Service Manual, p. 60-63 of 84. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.