Viessmann · Heat pump troubleshooting

Outdoor temperature sensor location and wiring

Vitocal 100-AW AM2V

What is going on

Mount the outdoor sensor on a north or north-west wall away from openings and heat sources, then run two-wire cable to the indoor unit.

Check in this order

  1. Mount on a north or north-westerly wall, 6-8 ft (2-2.5 m) above ground.
  2. In multi-storey buildings, mount in the upper half of the second floor.
  3. Do not mount above windows, doors or vents.
  4. Do not mount immediately below balconies or gutters.
  5. Never plaster over the sensor.
  6. Use two-wire cable up to 150 ft (50 m) long, 22 AWG (0.34 mm2).

Applies to: Vitocal 100-AW AM2V indoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.