Viessmann · Heat pump troubleshooting

Outdoor DC fan motor winding check

Vitocal IND-A

What is going on

Checks whether the fault is in the motor or in the outdoor PCB.

Check in this order

  1. Shut off the power.
  2. Release the UVW connector.
  3. Measure resistance U-V, U-W and V-W.
  4. If the three values are not equal, replace the fan motor.
  5. If the three values are equal, replace the outdoor PCB.

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.