Viessmann · Heat pump troubleshooting

Outdoor DC fan motor test

DLFSHC

What is going on

Test the outdoor DC fan motor windings, feedback signal and rotation voltages.

Check in this order

  1. Release the UVW connector. Measure resistance between U-V, U-W and V-W. If the three values are not equal, replace the fan motor.
  2. If they are equal, power on the unit. When it is in standby, measure voltage between pin 4 and pin 5 of the feedback connector. If it is not 5 V, replace the PCB.
  3. Rotate the fan by hand. Measure voltage from pin 1 to pin 5, pin 2 to pin 5 and pin 3 to pin 5. If any reading does not fluctuate in positive voltage, replace the fan motor.

Applies to: DLFSHC outdoor unit DC fan motor

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.