Viessmann · Heat pump troubleshooting
Outdoor DC fan motor test
What is going on
Test the outdoor DC fan motor windings, feedback signal and rotation voltages.
Check in this order
- Release the UVW connector. Measure resistance between U-V, U-W and V-W. If the three values are not equal, replace the fan motor.
- If they are equal, power on the unit. When it is in standby, measure voltage between pin 4 and pin 5 of the feedback connector. If it is not 5 V, replace the PCB.
- Rotate the fan by hand. Measure voltage from pin 1 to pin 5, pin 2 to pin 5 and pin 3 to pin 5. If any reading does not fluctuate in positive voltage, replace the fan motor.
Applies to: DLFSHC outdoor unit DC fan motor
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.