Optional electric strip heat accessory - overview and power supply
What is going on
A UL 1996 listed slip-in electric duct heater, installed by the licensed contractor in the supply duct downstream of the unit. It is ordered separately from Viessmann. The heat pump provides a 24 VAC AUX output that energizes the strip heater contactor. The heater high voltage comes from its own field supplied branch circuit and is not isolated by the heat pump disconnect.
Check in this order
- Install the heater in the supply duct downstream of the unit.
- Run a separate branch circuit with a fused disconnect sized to the heater data plate.
- Do not take heater line voltage from the heat pump supply, junction box or terminal blocks.
- Use the 24 VAC AUX output from the heat pump to control the heater contactor.
Applies to: Vitocal 100-WA with optional electric strip heat accessory
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.