Viessmann · Heat pump troubleshooting
Operating pressure too high or high pressure limit tripping
What is going on
High operating pressure or high pressure limit trip.
Likely causes
- Too little water flow in cool cycle
- Clogged air filter in heat cycle
- Air restriction in heat cycle
- Bad high pressure limit
- Unit overcharged
Check in this order
- Check loop pump and flow.
- Clean or replace the air filter.
- Check ductwork for a collapsed line.
- Replace the high pressure limit if faulty.
- Adjust the refrigerant charge.
Applies to: Vitocal 100-WA
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.