Opening the refrigerant circuit (R-454B flammable refrigerant)
What is going on
Use standard refrigerant work practice, but for flammable refrigerant follow the safe-handling sequence below before any repair that breaks into the circuit.
Check in this order
- Safely remove the refrigerant following local and national rules.
- Evacuate the circuit.
- Purge the circuit with inert gas (optional for A2L).
- Evacuate again (optional for A2L).
- If a flame is used to open the circuit, keep flushing or purging with inert gas.
- Open the circuit.
- Recover the charge into the correct recovery cylinders if venting is not allowed.
- Purge with oxygen-free nitrogen to make the appliance safe for flammable refrigerant. Vent down to atmospheric pressure before working.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Repeat as needed. Never use compressed air or oxygen to purge.
- Pressure-test with the purge gas before recharging. Leak-test after charging and before commissioning, and again before leaving the site.
Applies to: Vitocal 100-WA, AP1T models, R-454B refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.