Opening the refrigerant circuit (R-454B flammable refrigerant)

Vitocal 100-WA

What is going on

Use standard refrigerant work practice, but for flammable refrigerant follow the safe-handling sequence below before any repair that breaks into the circuit.

Check in this order

  1. Safely remove the refrigerant following local and national rules.
  2. Evacuate the circuit.
  3. Purge the circuit with inert gas (optional for A2L).
  4. Evacuate again (optional for A2L).
  5. If a flame is used to open the circuit, keep flushing or purging with inert gas.
  6. Open the circuit.
  7. Recover the charge into the correct recovery cylinders if venting is not allowed.
  8. Purge with oxygen-free nitrogen to make the appliance safe for flammable refrigerant. Vent down to atmospheric pressure before working.
  9. Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
  10. Repeat as needed. Never use compressed air or oxygen to purge.
  11. Pressure-test with the purge gas before recharging. Leak-test after charging and before commissioning, and again before leaving the site.

Applies to: Vitocal 100-WA, AP1T models, R-454B refrigerant circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.