Open loop well water requirements
What is going on
Use only a well of adequate capacity with good water quality. Do not pump pond or lake water through the unit. If groundwater may drop below 50°F (10°C) in heating season, calculate a higher flow rate. Install an 18-20 mesh strainer with isolation valves, and keep it accessible for cleaning. Discharge water to a well, creek, pond or other approved outlet, never directly to a sprinkler, and keep the line from freezing. Use 2-3 GPM/ton (7.5-11.5 LPM/3.5 kW) for open loops. Do not use PVC or CPVC on loop connections.
Likely causes
- Groundwater below 50°F during heating season
- Debris restricting the strainer
- Discharge restricted or connected to sprinkler
Check in this order
- Confirm the well capacity and water quality.
- Install an 18-20 mesh strainer with isolation valves.
- Route discharge to an approved outlet without restrictions and protect it from freezing.
- Set water flow at 2-3 GPM/ton.
- Clean or upsize the strainer if debris restricts flow.
Applies to: Open loop systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.