Open loop well water requirements

Vitocal 100-WA

What is going on

Use only a well of adequate capacity with good water quality. Do not pump pond or lake water through the unit. If groundwater may drop below 50°F (10°C) in heating season, calculate a higher flow rate. Install an 18-20 mesh strainer with isolation valves, and keep it accessible for cleaning. Discharge water to a well, creek, pond or other approved outlet, never directly to a sprinkler, and keep the line from freezing. Use 2-3 GPM/ton (7.5-11.5 LPM/3.5 kW) for open loops. Do not use PVC or CPVC on loop connections.

Likely causes

  • Groundwater below 50°F during heating season
  • Debris restricting the strainer
  • Discharge restricted or connected to sprinkler

Check in this order

  1. Confirm the well capacity and water quality.
  2. Install an 18-20 mesh strainer with isolation valves.
  3. Route discharge to an approved outlet without restrictions and protect it from freezing.
  4. Set water flow at 2-3 GPM/ton.
  5. Clean or upsize the strainer if debris restricts flow.

Applies to: Open loop systems

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.