Open loop flow rate and water valve control
What is going on
Flow is set by the modulating water valve. Size flow for open loop operation, and allow for higher flow if well water drops below 50°F (10°C) in the heating season.
Check in this order
- Set open loop flow to 2-3 GPM per ton (7.5-11.5 LPM per 3.5 kW).
- If groundwater may fall below 50°F (10°C) during heating season, calculate higher flow requirements.
- Use the water control valve at the unit outlet to keep pressure in the heat exchanger.
- Use either an ON/OFF two-position water valve or a proportional actuator with 2-10 VDC signal.
Applies to: Open loop systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.