Viessmann · Heat pump troubleshooting

Open loop flow rate and water valve control

Vitocal 100-WA

What is going on

Flow is set by the modulating water valve. Size flow for open loop operation, and allow for higher flow if well water drops below 50°F (10°C) in the heating season.

Check in this order

  1. Set open loop flow to 2-3 GPM per ton (7.5-11.5 LPM per 3.5 kW).
  2. If groundwater may fall below 50°F (10°C) during heating season, calculate higher flow requirements.
  3. Use the water control valve at the unit outlet to keep pressure in the heat exchanger.
  4. Use either an ON/OFF two-position water valve or a proportional actuator with 2-10 VDC signal.

Applies to: Open loop systems

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.