Viessmann · Heat pump troubleshooting

Nuisance tripping of the automatic limit (strip heater)

Vitocal 100-WA

What is going on

Most nuisance trips come from low airflow, poor heater placement, or high incoming air temperature.

Likely causes

  • Insufficient airflow across the heater
  • Heater located too close to a fan, damper, elbow, turn or transition
  • Inlet air temperature too high (110°F (43°C) or higher causes problems)

Check in this order

  1. Check airflow meets the heater minimum at high speed.
  2. Check heater placement against the required distances.
  3. Check the inlet air temperature at the heater is below 100°F (38°C).

Applies to: Optional electric strip heat accessory

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA installation, service and operating instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.