Viessmann · Heat pump troubleshooting

No domestic hot water

Vitocal 100-AW

What is going on

No hot water from the DHW tank.

Likely causes

  • Heat pump is switched off.
  • Controller settings were changed or are incorrect.
  • Display shows a Warning or Fault.

Check in this order

  1. Switch on the power.
  2. Switch on the main switch if fitted outside the mechanical room.
  3. Check the house fuse in the electrical switchboard.
  4. Start DHW heating and check the space heating or cooling time program, DHW setpoint, DHW time program and the clock.
  5. Run additional electric heating to heat DHW if needed.
  6. Read out and confirm the Warning or Fault.
  7. If needed, contact the heating contractor.

Applies to: Vitocal 100-AW AM2V

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.