Viessmann · Heat pump troubleshooting

Measuring signals on control boards

Vitocal IND-O

What is going on

Use these steps when a board check needs live readings.

Check in this order

  1. Disconnect the main power and remove the outdoor top cover. Check the outdoor board first where possible.
  2. Reconnect the main power.
  3. Probe board inputs and outputs with a digital multimeter using the wiring diagram.
  4. Red probe on the hot signal, black probe on ground or negative.
  5. Some DC signals pulse; the pulse should move steadily whenever a signal is present.
  6. For the indoor board, disconnect power, remove the front and control box covers, and lay the board face up on a plastic surface, not metal.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH service manual, PDF p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.