Viessmann · Heat pump troubleshooting

Leak detection for R32 systems

Vitocal 100-AW

What is going on

Approved leak detection methods for flammable refrigerant systems.

Check in this order

  1. Use an electronic leak detector suitable for R32 and free of potential ignition sources.
  2. Calibrate the detector in a refrigerant-free environment for the refrigerant used.
  3. Set the trip threshold to < 3 g/a, as printed in the manual.
  4. Use leak detection fluids only if they do not contain chlorine; chlorine-containing fluids can react with the refrigerant and cause rust.
  5. If a leak is found, put out any fire near the heat pump first.
  6. Do not solder leaks on the refrigeration circuit.

Applies to: R32 refrigeration circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.