Viessmann · Heat pump troubleshooting
IPM continuity check
What is going on
Procedure to check the IPM module continuity on the outdoor unit when an IPM-related fault (PC00) is present.
Check in this order
- Turn off the outdoor unit and disconnect the power supply.
- Discharge the electrolytic capacitors and make sure all stored energy is gone.
- Disassemble the outdoor PCB or the IPM board.
- Measure resistance between P and U, V, W, N, and between U, V, W and N, using the diode-style reference in Fig. 21.
- Compare readings with the reference table; replace the IPM board or outdoor PCB if they do not match.
Applies to: Outdoor IPM module, PC00 fault
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSHC Service Manual, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.