Inverter power module (IPM) continuity check
What is going on
Checks the IPM board for shorts or faults between the P, N, U, V and W terminals. The manual gives the expected reading as several megaohms.
Check in this order
- Turn off the outdoor unit and disconnect the power supply.
- Discharge the electrolytic capacitors and confirm all stored energy is gone.
- Disassemble the outdoor PCB or the IPM board.
- With a digital tester in diode/resistance mode, measure between P and U, V, W, N.
- Measure between U, V, W and N.
- Replace the module if the readings are not several megaohms.
Applies to: DLCSRB outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCSRB Service Manual, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.