Viessmann · Heat pump troubleshooting

Inverter power module (IPM) continuity check

Vitocal 100-S

What is going on

Checks the IPM board for shorts or faults between the P, N, U, V and W terminals. The manual gives the expected reading as several megaohms.

Check in this order

  1. Turn off the outdoor unit and disconnect the power supply.
  2. Discharge the electrolytic capacitors and confirm all stored energy is gone.
  3. Disassemble the outdoor PCB or the IPM board.
  4. With a digital tester in diode/resistance mode, measure between P and U, V, W, N.
  5. Measure between U, V, W and N.
  6. Replace the module if the readings are not several megaohms.

Applies to: DLCSRB outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCSRB Service Manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.