Installer-built (fabricated) manifold requirements

ECO HP

What is going on

If the WM Easy-Up manifold is not used, an installer-built manifold must meet these rules: at least 2 inches of vertical distance from the closely spaced tees to the first elbow on the heat pump piping (heat trap); a Y-strainer with an 80 mesh screen, mounted flow-down or horizontal; the heat pump circulator from the accessory box with its internal check valve fitted before the circulator is installed; common system piping of 1 inch or larger.

Check in this order

  1. Keep at least 2 inches of vertical run from the closely spaced tees to the first change of direction on the heat pump inlet/outlet piping.
  2. Install the Y-strainer with an 80 mesh screen, oriented flow-down or horizontal, to protect the heat pump heat exchanger.
  3. Fit the internal flow check valve into the heat pump circulator before mounting the circulator, and follow the circulator maker's guidelines.
  4. Use 1 inch or larger pipe for the common system piping.

Applies to: Heat pump installer-built manifold

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.