Viessmann · Heat pump troubleshooting
Install the pressure relief valve and discharge pipe
What is going on
Use the factory supplied pressure relief valve. Discharge must be piped safely to a floor drain, never outdoors.
Check in this order
- Fit the supplied pressure relief valve on the Supply from Outdoor Unit connection using the supplied fittings.
- Do not install any isolation valve between the heat pump and the pressure relief valve.
- Run the discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Keep the discharge pipe end unthreaded, do not reduce its diameter, and do not install a shutoff valve in it.
- Do not pipe the discharge to the outdoors.
- Position the discharge so it cannot scald people nearby.
Applies to: Indoor unit safety valve
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.