Install pressure relief valve and discharge pipe

Vitocal 100-AW

What is going on

Install the factory safety valve on the supply from the outdoor unit and pipe its discharge safely to ground level.

Likely causes

  • Scalding risk to people if discharge is not directed to the ground.
  • Air trapped in restrictive piping can stop the heat pump from purging.

Check in this order

  1. Use the supplied fittings to install the pressure relief valve on the supply from the outdoor unit.
  2. Fit the discharge pipe onto the relief valve so the pipe end is not threaded.
  3. Terminate the discharge pipe about 6 in (150 mm) above ground.
  4. Do not fit any shutoff valve in the discharge pipe.
  5. Keep the discharge pipe full diameter; do not reduce it.
  6. Do not install an isolation valve between the heat pump and the relief valve.
  7. Remove air through air vents in the system supply.
  8. Avoid restrictive piping in supply and return lines where air could be trapped.

Applies to: Outdoor unit AM2V 020028, 034043, 051078

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.