Install DHW temperature sensor
What is going on
Mount the DHW sensor on the tank so it reads true water temperature. Poor contact can let the system overheat the tank.
Check in this order
- Turn off power and fuel to the DHW tank.
- Remove the lower access panel below the display unit.
- Unscrew the sensor from the control board and extend the cable with field-supplied 18 AWG two-wire cable.
- Strip the sensor lead ends fully; they are left unstripped at the factory.
- Mount the sensor flat on the tank surface, vertically above or beside the bottom element, between steel tank and insulation.
- If insulation does not hold the sensor firmly, cover it with a 2 in (50 mm) square of adhesive insulation or aluminum duct tape.
- Route the cable back to the junction box and reconnect it to the control board.
Applies to: DHW tank installations
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 28-29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.