Viessmann · Heat pump troubleshooting
Indoor fan speed out of control protection (no code)
What is going on
If indoor fan speed stays below 300 RPM for 50 seconds, the fan shuts off and restarts 30 seconds later. After three restarts the unit stops and shows the failure.
Likely causes
- Indoor fan speed too low
Check in this order
- Check the indoor fan motor and its speed signal.
- Confirm the fan runs freely.
Applies to: DLFSOAH09XAK, DLFSOAH18XAK indoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.