Hydronic connection requirements
What is going on
Requirements for connecting the outdoor unit to the closed-loop heating system and protecting it from freezing and power loss.
Likely causes
- Vibration transmitted into the building piping if rigid connections are used.
- Freezing of the condenser if the unit is switched off in freezing outdoor temperatures.
- Freezing of the heating circuit if power fails and no antifreeze or isolation is used.
Check in this order
- Use a closed-loop hydronic system. Minimum heating medium pressure is 8 PSI (0.5 bar).
- Follow applicable hydronic standards.
- Size the connecting pipes to the indoor unit for adequate heating medium flow (see technical data table).
- Connect the heat pump to the hydronic system with flexible piping.
- Insulate heating medium pipes and connections.
- Do not switch off the unit when outdoor air is below freezing.
- If power failure is a risk, isolate the heat pump heating circuit from the hydronic module with an additional heat exchanger and fill the heat pump heating circuit with antifreeze.
- Install a solids separator at the unit inlet. This is a prerequisite for the warranty.
- Make the hydronic layout so the indoor unit can run the heating circuit without the outdoor unit.
Applies to: Outdoor unit AM2V 020028, 034043, 051078
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.