Viessmann · Heat pump troubleshooting

Hydronic connection requirements

Vitocal 100-AW

What is going on

Requirements for connecting the outdoor unit to the closed-loop heating system and protecting it from freezing and power loss.

Likely causes

  • Vibration transmitted into the building piping if rigid connections are used.
  • Freezing of the condenser if the unit is switched off in freezing outdoor temperatures.
  • Freezing of the heating circuit if power fails and no antifreeze or isolation is used.

Check in this order

  1. Use a closed-loop hydronic system. Minimum heating medium pressure is 8 PSI (0.5 bar).
  2. Follow applicable hydronic standards.
  3. Size the connecting pipes to the indoor unit for adequate heating medium flow (see technical data table).
  4. Connect the heat pump to the hydronic system with flexible piping.
  5. Insulate heating medium pipes and connections.
  6. Do not switch off the unit when outdoor air is below freezing.
  7. If power failure is a risk, isolate the heat pump heating circuit from the hydronic module with an additional heat exchanger and fill the heat pump heating circuit with antifreeze.
  8. Install a solids separator at the unit inlet. This is a prerequisite for the warranty.
  9. Make the hydronic layout so the indoor unit can run the heating circuit without the outdoor unit.

Applies to: Outdoor unit AM2V 020028, 034043, 051078

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.