Viessmann · Heat pump troubleshooting
Heating water piping and connections (indoor unit)
What is going on
Piping must be supported by hangers, never by the indoor unit or its components. Use isolation valves so system parts can be serviced on their own. Flush the heating system before connecting the heat pump, especially on an existing system.
Check in this order
- Thoroughly flush the heating system, particularly before connecting to an existing system.
- Connect the indoor unit to the heating system.
- Use approved pipe sealant or Teflon tape on the installation fittings.
- Use the two-wrench method when tightening fittings: one wrench holds the pipe, the other turns the fitting.
- Keep the heating water maximum allowable working pressure at or below 30 psig (2 bar).
- Keep at least 2 in. (50 mm) between uninsulated hot water pipes and combustible material, unless the pipe has suitable insulation (follow local rules).
- If no DHW tank is connected, close the DHW tank supply connection with a cap.
- Install a field-supplied temperature gauge in the supply piping near the heat pump.
Applies to: Indoor unit heating water and DHW connections
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.