Weil-McLain · Heat pump troubleshooting

General troubleshooting checks before diagnosing codes

ECO HP

What is going on

Do a visual inspection first. Shut off power before opening internal components.

Likely causes

  • Loose connections or defective wiring.
  • Blown fuses or a safety device that has tripped.
  • Faulty temperature sensors.

Check in this order

  1. Check the error and lockout histories and read the most recent items.
  2. Use a voltmeter to confirm 120 Vac to the boiler and the HP indoor unit, and 240 Vac to the heat pump outdoor unit.
  3. Confirm the thermostat is calling for heat and 24 Vac is present between thermostat wires and ground.
  4. Confirm no safety device has tripped. Find the cause before resetting it. Never bridge safety devices or change them from factory settings.
  5. Confirm all control connectors are fully seated.
  6. Replace any blown fuses.
  7. Check temperature sensors against known temperatures and their resistance readings.
  8. If a pressure relief valve is replaced, reconnect its drain piping.

Applies to: ECO HP split air-to-water heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.