General troubleshooting checks before diagnosing codes
What is going on
Do a visual inspection first. Shut off power before opening internal components.
Likely causes
- Loose connections or defective wiring.
- Blown fuses or a safety device that has tripped.
- Faulty temperature sensors.
Check in this order
- Check the error and lockout histories and read the most recent items.
- Use a voltmeter to confirm 120 Vac to the boiler and the HP indoor unit, and 240 Vac to the heat pump outdoor unit.
- Confirm the thermostat is calling for heat and 24 Vac is present between thermostat wires and ground.
- Confirm no safety device has tripped. Find the cause before resetting it. Never bridge safety devices or change them from factory settings.
- Confirm all control connectors are fully seated.
- Replace any blown fuses.
- Check temperature sensors against known temperatures and their resistance readings.
- If a pressure relief valve is replaced, reconnect its drain piping.
Applies to: ECO HP split air-to-water heat pump
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.