Viessmann · Heat pump troubleshooting

Freeze stat lockout on open loop

Vitocal 100-WA

What is going on

The freeze stat protects the liquid-to-refrigerant heat exchanger from freezing. It reads refrigerant temperature leaving the water coil in heating mode. If that temperature drops below the freeze set point, the unit locks out and must be reset manually.

Likely causes

  • Low water flow or too low water temperature from the well.
  • Heat exchanger scaling or debris restricting flow.

Check in this order

  1. Check strainer for debris and clean it.
  2. Confirm well flow meets 2-3 GPM per ton.
  3. Check water quality against the acceptable range before reset.
  4. Reset the freeze lockout manually once the cause is cleared.

Applies to: Open loop systems in heating mode

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.