Weil-McLain · Heat pump troubleshooting
Freeze protection and antifreeze dosing
What is going on
Use only antifreeze listed by WM Technologies for the ECO HP. Never exceed 50% by volume.
Likely causes
- Antifreeze that is too strong slows heat transfer and can form sludge in the heat pump.
- Glycol and inhibitor levels drop over time and can leak out before water does.
Check in this order
- Flush any system that has used glycol before installing the heat pump.
- Check the antifreeze and inhibitor levels at least once a year.
- If using automatic fill with antifreeze, install a water meter to watch make-up water.
- Find the concentration needed for the lowest likely temperature from the antifreeze container data.
- Add up the system volume, including the expansion tank and the heat pump (0.41 gal).
- Multiply the total volume by the required percentage to get gallons of antifreeze.
Applies to: ECO HP split air-to-water heat pump
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, pp. 59-60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.