Freeze protection and antifreeze dosing

ECO HP

What is going on

Use only antifreeze listed by WM Technologies for the ECO HP. Never exceed 50% by volume.

Likely causes

  • Antifreeze that is too strong slows heat transfer and can form sludge in the heat pump.
  • Glycol and inhibitor levels drop over time and can leak out before water does.

Check in this order

  1. Flush any system that has used glycol before installing the heat pump.
  2. Check the antifreeze and inhibitor levels at least once a year.
  3. If using automatic fill with antifreeze, install a water meter to watch make-up water.
  4. Find the concentration needed for the lowest likely temperature from the antifreeze container data.
  5. Add up the system volume, including the expansion tank and the heat pump (0.41 gal).
  6. Multiply the total volume by the required percentage to get gallons of antifreeze.

Applies to: ECO HP split air-to-water heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, pp. 59-60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.