Fill, test and purge air from the water system
What is going on
Fill only after the water meets the manual's requirements. Eliminate all leaks, because make-up water shortens heat pump and boiler life.
Likely causes
- Trapped air restricts flow and can trigger the water flow failure codes.
Check in this order
- Close the manual and automatic air vents and the heat pump drain valve.
- Fill to the correct cold-fill pressure for the application (typically 12 psi residential).
- Check for leaks at fill and during startup. Repair all leaks before continuing.
- Connect a hose to the system purge valve and route it to a drain you can see.
- Close the heat pump or system isolation valve between the purge valve and the fill connection.
- Close zone isolation valves. Open the quick-fill valve and the purge valve.
- Open one zone isolation valve at a time and purge until no air flow shows. Close it and move to the next zone.
- Purge the boiler and its internal piping the same way.
- Close the quick-fill and purge valves, remove the hose and open all isolation valves.
- Bleed remaining air at manual vents, starting at the lowest floor. Open the automatic air vent one turn if the system has one.
- Refill to the correct pressure. Operating pressure must never exceed 24 psi.
Applies to: ECO HP split air-to-water heat pump
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.