Viessmann · Heat pump troubleshooting

Fan operates but compressor does not

Vitocal 100-WA

What is going on

Fan runs and compressor is off.

Likely causes

  • Thermostat not set properly
  • Low or high pressure limit tripped or locked out
  • Internal protector operating
  • Faulty internal protector
  • Freeze protector activated (well water only)
  • Defective compressor drive
  • Defective compressor
  • Gas leak detection

Check in this order

  1. Read the thermostat instructions and set correctly.
  2. Repair the condition causing excessive pressures.
  3. Repair the condition causing extreme temperatures.
  4. Replace the compressor if the internal protector is faulty.
  5. Check water flow or replace the freeze protector.
  6. Replace the compressor drive.
  7. Replace the compressor.
  8. If GAS is shown, refer to the leak mitigation check.

Applies to: Vitocal 100-WA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.